Circadian Sky

Drywall Deep Regress
Lay-In Array

Installation Manual
Isometric view of a six-fixture CS12 lay-in array in a drywall coffer
Six CS12 fixtures installed as a lay-in array in a drywall coffered ceiling

This manual covers the mechanical installation of Circadian Sky fixtures as a deep regress lay-in array in a drywall coffered ceiling. Fixtures are laid into a site-built coffer, similar to lay-in ceiling tiles, with no fixture-side hardware required. The six-fixture CS12 array is shown as the worked example, but the same approach applies to every Circadian Sky fixture size and any array length (see the Circadian Lab previews on the following pages). For electrical wiring and lighting controls, refer to the standard Circadian Sky Installation Manual.

At a glance

Fixture sizesAny Circadian Sky size: CS12 (1×2 ft), CS14 (1×4 ft), CS154 (1.5×4 ft), CS22 (2×2 ft), CS24 (2×4 ft), CS44 (4×4 ft, ships 2027)
Array patternsButted end to end (narrow linear strip) or side by side (wider skylight panel); butted fixtures share one continuous slot
Housing depth3-5/16" (84 mm), all sizes
Fixture weightCS12 7.3 lbs, CS14 25.1 lbs, CS154 33.7 lbs, CS22 24 lbs, CS24 43.7 lbs, CS44 82 lbs est. (excluding framing and drywall)
Overhead clearanceRegress depth plus about 6" (≥ 9-1/2" to 10" with the 4-1/8" example build-up); see the clearance matrix
Worked example in this manualSix CS12 fixtures butted end to end: spec code CS-12-RG-INT-XX-XX-XX, group window 140-5/8" × 8-1/8", overall length 144-9/16" including trim, 43.8 lbs total

Works with every Circadian Sky size

The lay-in detail in this manual is not specific to the CS12. Any Circadian Sky fixture size can be installed the same way: size the coffer slot for the fixture row, allow overhead clearance for the lay-in rotation (see the clearance table after these previews), and lay the fixtures in through the opening. Fixtures can be butted end to end (short ends touching) for a narrow linear strip, or side by side (long edges touching) for a wider skylight panel; either way the butted fixtures share one continuous slot.

Explore each configuration in Circadian Lab, Innerscene's free lighting design tool. Each preview below opens an interactive 3D room with the array installed in a drywall coffer and the calculated light rendered on the floor, walls and ceiling. The previews model the example build-up from this manual: 2×4 framing on edge (3-1/2" actual) plus 5/8" drywall, a 4-1/8" regress. Click a preview to open it.

Circadian Lab 3D view: CS24 (2×4 ft) lay-in array, 3 fixtures butted end to end
3D view
Circadian Lab 2D plan: CS24 (2×4 ft) lay-in array, 3 fixtures butted end to end
2D plan
CS24 (2×4 ft)
3 fixtures butted end to end
Opens in Circadian Lab
Circadian Lab 3D view: CS24 (2×4 ft) lay-in array, 3 fixtures butted side by side
3D view
Circadian Lab 2D plan: CS24 (2×4 ft) lay-in array, 3 fixtures butted side by side
2D plan
CS24 (2×4 ft)
3 fixtures butted side by side
Opens in Circadian Lab
Circadian Lab 3D view: CS154 (1.5×4 ft) lay-in array, 3 fixtures butted end to end
3D view
Circadian Lab 2D plan: CS154 (1.5×4 ft) lay-in array, 3 fixtures butted end to end
2D plan
CS154 (1.5×4 ft)
3 fixtures butted end to end
Opens in Circadian Lab
Circadian Lab 3D view: CS154 (1.5×4 ft) lay-in array, 3 fixtures butted side by side
3D view
Circadian Lab 2D plan: CS154 (1.5×4 ft) lay-in array, 3 fixtures butted side by side
2D plan
CS154 (1.5×4 ft)
3 fixtures butted side by side
Opens in Circadian Lab

Circadian Lab previews (continued)

Circadian Lab 3D view: CS22 (2×2 ft) lay-in array, 5-fixture row
3D view
Circadian Lab 2D plan: CS22 (2×2 ft) lay-in array, 5-fixture row
2D plan
CS22 (2×2 ft)
5-fixture row
Opens in Circadian Lab
Circadian Lab 3D view: CS14 (1×4 ft) lay-in array, 3 fixtures butted end to end
3D view
Circadian Lab 2D plan: CS14 (1×4 ft) lay-in array, 3 fixtures butted end to end
2D plan
CS14 (1×4 ft)
3 fixtures butted end to end
Opens in Circadian Lab
Circadian Lab 3D view: CS14 (1×4 ft) lay-in array, 3 fixtures butted side by side
3D view
Circadian Lab 2D plan: CS14 (1×4 ft) lay-in array, 3 fixtures butted side by side
2D plan
CS14 (1×4 ft)
3 fixtures butted side by side
Opens in Circadian Lab
Circadian Lab 3D view: CS12 (1×2 ft) lay-in array, 6 fixtures butted end to end
3D view
Circadian Lab 2D plan: CS12 (1×2 ft) lay-in array, 6 fixtures butted end to end
2D plan
CS12 (1×2 ft)
6 fixtures butted end to end
Opens in Circadian Lab
Circadian Lab 3D view: CS12 (1×2 ft) lay-in array, 6 fixtures butted side by side
3D view
Circadian Lab 2D plan: CS12 (1×2 ft) lay-in array, 6 fixtures butted side by side
2D plan
CS12 (1×2 ft)
6 fixtures butted side by side
Opens in Circadian Lab

Inspiration

Nursing station with a lay-in Circadian Sky array recessed in a drywall soffit alongside a standard grid ceiling
A lay-in Circadian Sky array over a nursing station, set in a drywall soffit alongside the standard grid ceiling
Circadian Lab sidebar with the Regress field circled

Try it in Circadian Lab

Every Circadian Lab preview on the previous pages opens with the array already selected. Edit the Regress field in the sidebar (circled) to see the effect of a deeper or shallower coffer on the room, and use the clearance matrix to check the plenum space that choice needs.

Clearance for the lay-in rotation

The fixture housing is wider than the window opening, so it only passes through the coffer tilted. It threads up through the window at a steep roll, then levels out while its lower edge stays dipped in the opening, sliding sideways over the ceiling as it flattens. The matrix below gives the minimum clearance between the finished ceiling and the structure above for this maneuver, including a 1" working margin. It assumes open plenum space beside the coffer; deeper coffers need more room almost inch for inch. Thread fixtures through a multi-cell opening lengthwise (insert the last two fixtures together before sliding the second-to-last into its cell).

Fixture sizeHousing cross-sectionWindow opening2×4 + 5/8″ drywall (4-1/8″ regress)2×6 + 5/8″ drywall (6-1/8″ regress)2×12 + 5/8″ drywall (11-7/8″ regress)
CS14 / CS154 / CS24 side by side · CS44 either way (ships 2027)46-7/8″ × 3-5/16″43-3/4″≥ 9″≥ 11″≥ 16-3/4″
CS22 · CS24 end to end · CS12 side by side23-1/4″ × 3-5/16″20-1/8″≥ 9-1/2″≥ 11-1/2″≥ 17-1/4″
CS154 end to end17-1/4″ × 3-5/16″14-1/8″≥ 9-1/2″≥ 11-1/2″≥ 17-1/4″
CS12 / CS14 end to end11-1/4″ × 3-5/16″8-1/8″≥ 10″≥ 12″≥ 17-3/4″

Clearance is measured from the finished ceiling face to the underside of the structure above. Rule of thumb: regress depth plus about 6". Use the interactive simulation on the next page to scrub through the maneuver; the worst-case drawings show the binding position for each size.

Cross-section drawing of a CS12 or CS14 fixture rolled 35 degrees, lower edge dipped through the window, at the tightest point of the level-out
Worst-case position, 11-1/4″ crossing the slot: CS12 / CS14 end to end

Interactive clearance simulation

Scrub the time slider to step through the lay-in maneuver, drag to orbit, and switch fixture size, array orientation and regress depth to see the clearance each combination needs. The printed manual shows the worst-case side profile for the selected configuration.

Worst-case positions, continued (4-1/8″ regress build-up)

Cross-section drawing of a CS154 fixture rolled 26 degrees, lower edge dipped through the window, at the tightest point of the level-out
Worst-case position, 17-1/4″ crossing the slot: CS154 end to end
Cross-section drawing of a CS22 or CS24 fixture rolled 20 degrees, lower edge dipped through the window, at the tightest point of the level-out
Worst-case position, 23-1/4″ crossing the slot: CS22, CS24 end to end, CS12 side by side (see the sizing table for the 46-7/8″ side-by-side crossing, which also covers the CS44 in either orientation)

Array overview

Isometric view of the six-fixture array from above, without framing, with housing and trim callouts
Figure 1: Isometric view from above, without framing
Reflected ceiling plan of six CS12 fixtures without drywall, with nominal and exact dimensions
Figure 2: Reflected Ceiling Plan (RCP) without drywall, shown with six CS12 fixtures

Individual window size: 20-1/8" × 8-1/8" nominal (20.14" × 8.13" exact)

Group window size: 140-5/8" × 8-1/8" nominal (140.61" × 8.13" exact)

Array with framing and drywall

Cross-section through the coffer with a fixture installed: structure, hanger wire, grid clip, housing resting on perimeter straps, framing and drywall
Coffer cross-section with fixture installed (CS12 shown; see the sizing table for all sizes)
Reflected ceiling plan of six CS12 fixtures with drywall
Reflected Ceiling Plan (RCP) with drywall, six-CS12 worked example

Materials and coffer sizing

Fixture dimensions

Fixture sizeVisible glass (W × L)Overall including trim (W × L)
CS12 (1×2 ft)8.33″ × 20.14″11.93″ × 23.74″
CS14 (1×4 ft)8.33″ × 43.76″11.93″ × 47.36″
CS154 (1.5×4 ft)14.12″ × 44.12″17.72″ × 47.72″
CS22 (2×2 ft)20.14″ × 20.14″23.74″ × 23.74″
CS24 (2×4 ft)20.14″ × 43.76″23.74″ × 47.36″
CS44 (4×4 ft, ships 2027)43.76″ × 43.76″47.36″ × 47.36″

Trim is 1.80" wide on all sides and overlaps a ceiling cut-out by up to 0.26" per side; housing depth is 3.60" (3.68" minimum recess including the rear screw heads). When tiling multiple fixtures, allow an additional 1/16" margin between adjacent trims. Dimensions per the Circadian Sky Dimensional Drawings (all sizes).

Typical materials

  • Drywall: e.g. 5/8" gypsum board
  • Well liner: e.g. 1/2" gypsum board on the reveal walls, finished flat white to match the trim
  • Framing: e.g. 2" × 4" lumber
  • Perimeter support: e.g. Simpson Strong-Tie 25-ft 16-gauge galvanized steel coiled strap, wood to wood, model CS16-R (Lowe's item #1944384)

Coffer sizing for every fixture size

The six-CS12 array in the figures is a worked example; the same detail applies to every Circadian Sky size. Housing depth is 3-5/16" for all sizes. The window opening is the finished glass-flush slot; butted fixtures share one continuous slot that spans from glass to glass across the butt joints (the six-CS12 example's group window is 140-5/8" × 8-1/8"). Where the well walls are lined with drywall, frame the rough opening larger by twice the liner thickness so the finished opening still matches these values. The Circadian Lab previews compute the slot for any array automatically.

Fixture sizeHousing (W × L)Window opening (W × L)WeightMin clearance, end to end*Min clearance, side by side*
CS12 (1×2 ft)11-1/4″ × 23-1/4″8-1/8″ × 20-1/8″7.3 lbs≥ 10″≥ 9-1/2″
CS14 (1×4 ft)11-1/4″ × 47-1/4″8-1/8″ × 44-1/8″25.1 lbs≥ 10″≥ 9″
CS154 (1.5×4 ft)17-1/4″ × 47-1/4″14-1/8″ × 44-1/8″33.7 lbs≥ 9-1/2″≥ 9″
CS22 (2×2 ft)23-1/4″ × 23-1/4″20-1/8″ × 20-1/8″24 lbs≥ 9-1/2″≥ 9-1/2″
CS24 (2×4 ft)23-1/4″ × 47-1/4″20-1/8″ × 44-1/8″43.7 lbs≥ 9-1/2″≥ 9″
CS44 (4×4 ft, ships 2027)47-1/4″ × 47-1/4″44-1/8″ × 44-1/8″82 lbs (est.)≥ 9″≥ 9″

* Overhead clearance for the lay-in rotation at the 4-1/8" example regress, by array orientation: end to end puts the short housing side across the slot, side by side the long side (a wider crossing dimension rolls less, so it needs slightly less height). For deeper regress values see the clearance matrix.

Side and end views

Side view of the full array with the Figure 6 close-up region marked
Figure 5: Side view

Total weight: 7.3 lbs × 6 = 43.8 lbs (excluding framing and drywall)

Side view close-up showing structure, housing, perimeter support, framing and drywall layers with minimum clearances
Figure 6: Side view close-up
End view showing at least 13 inches of clearance for lay-in installation
Figure 7: End view

Figures 6 and 7 show the CS12 example. Required overhead clearance depends on fixture size and regress depth, see the clearance matrix: with this manual's 4-1/8" regress build-up, allow at least 10" for the CS12.

Cross sections

Cross section A-A through the length of the array
Figure 8: Cross section A-A
Cross section B-B showing housing and trim, perimeter support, framing, drywall and corner bead
Figure 9: Cross section B-B

Finish the coffer edges with a sharp drywall corner bead, e.g. Trim-Tex RJ10LP or similar, for a crisp shadow line around the window opening.

Pre-installation checklist

  • Framing safely supports the full array weight (43.8 lbs) plus drywall.
  • Finished drywall is straight and level along the coffer.
  • Overhead clearance for the lay-in rotation per the clearance matrix (10" for the CS12 with the 4-1/8" regress build-up).
  • Perimeter support is installed around the coffer opening (see Figure 3).
  • Coffer edges are finished with a sharp drywall corner bead (see Figure 9).
  • Power and control wiring is pulled to the fixture locations (see the standard Circadian Sky Installation Manual).

Installation steps

1) Prepare the drywall coffered ceiling as shown below. Ensure the framing can safely support the weight of the fixtures and that the finished drywall is straight.

Isometric view of the empty coffer from above, without fixtures
Figure 10: Isometric view from above, without fixtures
Isometric view of the empty coffer from below, without fixtures
Figure 11: Isometric view from below, without fixtures

2) Lay in each fixture, similar to a lay-in ceiling tile, by angling it through the coffer opening.

Isometric view from above while a fixture is angled through the coffer opening
Figure 12: Isometric view from above while laying in a fixture
Isometric view from above with one fixture installed
Figure 13: Isometric view from above with one fixture installed

3) Move the fixture into its final position, then repeat for all remaining fixtures. If necessary, secure each fixture to the framing with ties.

Isometric view from above with all six fixtures installed
Figure 14: Isometric view from above with all fixtures

4) For electrical wiring and lighting controls, refer to the standard Circadian Sky Installation Manual.

Isometric view from below with all six fixture windows visible
Figure 15: Isometric view from below with all fixtures